No products in the cart.
new-32%On Sale
Schneider G12F3A125 | Circuit breaker, GoPact MCCB 125, 3 poles, 30kA at 415VAC, 125A rating, TMD trip unit, adjustable thermal protection
G12F3A125
Description
Schneider G12F3A125 | Circuit breaker, GoPact MCCB 125, 3 poles, 30kA at 415VAC, 125A rating, TMD trip unit, adjustable thermal protection
Schneider G12F3A125 Description
Introduction
This product is part of the new GoPact Molded Case Circuit Breakers range (MCCB). It is a complete 3 poles circuit breaker made of a 125A breaker frame and of a thermal magnetic trip unit (TMD). GoPact MCCB has a good price-performance ratio for basic applications and delivers a reliable electrical protection for your applications. The breaking capacity (Icu) is 30kA rms at 415VAC 50/60Hz.
The operational voltage is 415VAC 50/60Hz. This product embeds a 125A rating (In) thermal-magnetic trip unit (TMD). This TMD trip unit provides an adjustable thermal protection Ir (against overloads) with a setting range from 0.8xIn to 1xIn (100A-125A). And it provides a fixed magnetic (against short-circuits) protection set to 10xIn (1250A). GoPact MCCB comes with a variety of optional accessories simple to choose and to install.
Product dimensions are 75mm (Width) x 130mm (Height) x 60mm (Depth). The weight is 0.7 kg. GoPact MCCB 125 is IEC 60947-1 and IEC 60947-2 certified. GoPact MCCB range benefits from Schneider Electric quality assurance.
- Understanding the Significance of Schneider G12F3A125
- Exploring Its Design and Functionality
- The Importance of Efficient Electrical Distribution Systems
Features and Specifications
- Delving into the Technical Specifications
- Highlighting Key Features of the Schneider G12F3A125
- Capacity and Power Ratings
- Design and Construction
- Safety Features
- Compatibility and Integration
Applications and Industries
- Diverse Applications Across Various Industries
- Role of Schneider G12F3A125 in Commercial Settings
- Impact on Industrial Operations and Efficiency
Advantages of Schneider G12F3A125
- Enhanced Safety Protocols for Electrical Systems
- Increased Reliability and Durability
- Optimal Performance in Dynamic Environments
- Cost-Effectiveness and Long-Term Savings
Installation and Maintenance
- Step-by-Step Installation Guide
- Routine Maintenance Procedures
- Troubleshooting Common Issues
- Importance of Professional Assistance
Comparison with Competing Products
- Assessing Schneider G12F3A125 Against Market Competitors
- Identifying Unique Selling Points
- Addressing Limitations and Areas for Improvement
Customer Reviews and Testimonials
- Real-Life Experiences Shared by Users
- Positive Feedback on Performance and Reliability
- Areas of Improvement as Suggested by Customers
Future Prospects and Innovations
- Anticipated Upgrades and Enhancements
- Integration with Smart Technologies
- Contribution to Sustainable Energy Practices
Conclusion
- Recapitulating the Key Attributes of Schneider G12F3A125
- Emphasizing Its Role in Modern Electrical Systems
- Encouraging Further Exploration and Adoption
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | GoPact MCCB |
|---|---|
| product or component type | Circuit breaker |
| Product name | GoPact MCCB 125 |
| Device application | Distribution |
| poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 125 A at 40 °C |
| [Ue] rated operational voltage | 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 30 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Performance level | F 30 kA 380/415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 440 V AC conforming to EN/IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Mechanical durability | 30000 cycles |
| Electrical durability | 5000 cycles at 415 V In |
| Power dissipation per pole | 18.7 W |
| mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| downside connection | Front |
| Connection terminals | Screw terminals |
| Connection pitch | 25 mm |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rating | 125 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.8...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 10 x In |
| Width (W) | 75 mm |
| Height (H) | 130 mm |
| Depth (D) | 60 mm |
| net weight | 0.7 kg |
| Colour | Grey (RAL 7035) |
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H |
|---|---|
| Overvoltage category | III |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…55 °C |
| ambient air temperature for storage | -35…85 °C |
| Operating altitude | 0...2000 m without derating 2000...5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 12.4 cm |
| Package 1 Width | 8.5 cm |
| Package 1 Length | 13.9 cm |
| Package 1 Weight | 908 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 7.579 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 128 |
| Package 3 Height | 75 cm |
| Package 3 Width | 60 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 129.764 kg |
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Be the first to review “Schneider G12F3A125 | Circuit breaker, GoPact MCCB 125, 3 poles, 30kA at 415VAC, 125A rating, TMD trip unit, adjustable thermal protection” Cancel reply
Reviews
There are no reviews yet.