Schneider G80H3E630 |Circuit breaker, GoPact MCCB 800, 3 poles, 70kA at 415VAC, 630A rating, ETU trip unit, adjustable thermal protection

Technical Specifications G80H3E630

  • Type: Molded Case Circuit Breaker (MCCB), GoPact series.

  • Number of Poles: 3 poles.

  • Rated Current: 630 Amperes.

  • Breaking Capacity: 70 kiloamperes (kA) at 415 Volts AC.

  • Trip Unit: ETU (Electronic Trip Unit) for precise and advanced protection.

  • Adjustable Thermal Protection: Allows setting the thermal trip according to system requirements.

  • Rated Voltage: Designed for operation at 415 VAC.

  • Durability: Built for high reliability in demanding industrial environments.

Key Features

  • Advanced Protection: The ETU electronic trip unit offers multi-level protection against overloads, short circuits, and phase failures.

  • Adjustable Thermal Settings: Enables customization of thermal protection thresholds to match different application needs.

  • High Breaking Capacity: Capable of interrupting fault currents up to 70kA, providing robust protection against severe electrical faults.

  • Rugged Construction: Manufactured with high-quality materials ensuring long life and stable performance under tough conditions.

  • Easy Installation and Maintenance: Designed for quick installation and accessible trip unit for easy adjustments or maintenance.

  • Compatibility: Can be integrated seamlessly into modern electrical distribution and protection systems.

Applications

  • Industrial Electrical Panels: Ideal for protecting circuits in factories and heavy industrial installations.

  • Electrical Distribution Systems: Suitable for use in low and medium voltage distribution boards.

  • Commercial Buildings and Large Facilities: Provides dependable protection for high-demand electrical loads.

  • Engineering Projects: Used in large-scale electrical infrastructure projects requiring reliable and flexible circuit protection.

  • Transformer and Motor Protection: Protects transformers and motors from overload and short circuit faults, extending equipment lifespan.

  • Variable Protection Requirements: Perfect for environments where adjustable protection settings are necessary due to changing operating conditions.

Additional information

brands

Schneider Electric

Specifications

Main
Range of product GoPact MCCB
product or component type Circuit breaker
Product name GoPact MCCB 800
Device application Distribution
poles description 3P
Protected poles description 3D
[In] rated current 630 A at 40 °C
[Ue] rated operational voltage 415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 70 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 80 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Performance level H 70 kA 380/415 V AC
Trip unit name ETU
Trip unit technology Electronic
Trip unit protection functions LSI
Control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 440 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity 70 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 80 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Mechanical durability 15000 cycles
Electrical durability 3000 cycles at 415 V In
Power dissipation per pole 50 W
mounting support Backplate
Mounting position Horizontal and vertical Flat on the back
Upside connection Front
downside connection Front
Connection terminals Screw terminals
Connection pitch 60 mm
Protection type L : for overload protection (thermal) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Trip unit rating 630 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.25...1 x In
Long-time protection delay adjustment type tr Fixed
Short-time protection pick-up adjustment type Isd Adjustable
[Isd] Short-time protection pick-up adjustment range 1.5...10 x Ir
Short-time protection delay adjustment type tsd Fixed
Instantaneous protection pick-up adjustment type Ii Adjustable
[Ii] instantaneous protection pick-up adjustment range 1.5...10 x In
Width (W) 180 mm
Height (H) 250 mm
Depth (D) 105 mm
net weight 6.9 kg
Colour Grey (RAL 7035)
Environment
Standards EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
Overvoltage category III
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP20 conforming to IEC 60529
Ambient air temperature for operation -20…55 °C
ambient air temperature for storage -35…85 °C
Operating altitude 0...2000 m without derating 2000...5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 29.4 cm
Package 1 Width 29.8 cm
Package 1 Length 39.8 cm
Package 1 Weight 10.01 kg
Unit Type of Package 2 P06
Number of Units in Package 2 12
Package 2 Height 105 cm
Package 2 Width 60 cm
Package 2 Length 80 cm
Package 2 Weight 25.804 kg

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider G80H3E630 |Circuit breaker, GoPact MCCB 800, 3 poles, 70kA at 415VAC, 630A rating, ETU trip unit, adjustable thermal protection”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare