Description

Technical Specifications G80N3TM630

  • Product Model: Schneider G80N3TM630

  • Type: MCCB – Molded Case Circuit Breaker

  • Number of Poles: 3 poles

  • Breaking Capacity: 50 kA at 415V AC

  • Rated Current: 630 Amps

  • Trip Unit: TMD (Thermal Magnetic Device)

  • Thermal Protection: Adjustable

  • Magnetic Protection: Fixed

  • Operating Voltage Range: Up to 690V AC

  • Frequency: 50/60 Hz

  • Insulation Voltage: 800V

  • Rated Impulse Withstand Voltage (Uimp): 8 kV

  • Utilization Category: A (as per IEC 60947-2)

  • Degree of Protection: IP40 (when mounted in a suitable enclosure)

  • Standards: IEC 60947-2 compliant

Key Features and Benefits

  1. Robust Protection System:
    Provides both thermal (overload) and magnetic (short circuit) protection to ensure safe operation under fault conditions.

  2. Adjustable Thermal Trip:
    The thermal protection can be fine-tuned to match the specific load characteristics and system requirements, offering flexibility in diverse installations.

  3. Reliable Breaking Capacity:
    With a 50 kA breaking capacity at 415VAC, it offers dependable protection in medium-to-high fault level environments.

  4. Efficient Design:
    Compact and modular design helps save panel space and simplifies integration into existing switchboards or panels.

  5. Maintenance-Friendly:
    Designed with installer convenience in mind, offering accessible terminals, visible indicators, and straightforward mounting.

  6. Durable Build Quality:
    Manufactured with high-quality materials that ensure long service life and reliable performance under demanding conditions.

Typical Applications

  • Industrial switchboards for machinery and plant equipment

  • Power distribution systems in commercial buildings, offices, and shopping centers

  • Utility panels in warehouses and factories

  • Backup and generator protection systems

  • Energy systems in infrastructure projects such as airports, hospitals, and data centers

  • Renewable energy installations, including solar PV arrays and small wind systems

Additional information

brands

Schneider Electric

Specifications

Main
Range of product GoPact MCCB
product or component type Circuit breaker
Product name GoPact MCCB 800
Device application Distribution
poles description 3P
Protected poles description 3D
[In] rated current 630 A at 40 °C
[Ue] rated operational voltage 415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 50 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Performance level N 50 kA 380/415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 440 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity 50 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Mechanical durability 15000 cycles
Electrical durability 3000 cycles at 415 V In
Power dissipation per pole 60 W
mounting support Backplate
Mounting position Horizontal and vertical Flat on the back
Upside connection Front
downside connection Front
Connection terminals Screw terminals
Connection pitch 60 mm
Protection type L : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating 630 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.7...1 x In
Long-time protection delay adjustment type tr Fixed
Instantaneous protection pick-up adjustment type Ii Fixed
[Ii] instantaneous protection pick-up adjustment range 10 x In
Width (W) 180 mm
Height (H) 250 mm
Depth (D) 105 mm
net weight 6.9 kg
Colour Grey (RAL 7035)
Environment
Standards EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
Overvoltage category III
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP20 conforming to IEC 60529
Ambient air temperature for operation -20…55 °C
ambient air temperature for storage -35…85 °C
Operating altitude 0...2000 m without derating 2000...5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 18 cm
Package 1 Width 27 cm
Package 1 Length 29 cm
Package 1 Weight 11050 g
Unit Type of Package 2 P06
Number of Units in Package 2 12
Package 2 Height 105 cm
Package 2 Width 60 cm
Package 2 Length 80 cm
Package 2 Weight 146.392 kg

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider G80N3TM630 | Circuit breaker, GoPact MCCB 800, 3 poles, 50kA at 415VAC, 630A rating, TMD trip unit, adjustable thermal protection”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare