Schneider RE48ACV12MW | Asymmetrical flashing relay – 0.02 s..300 h – 24..240 V AC – 2 OC
Description
Schneider RE48ACV12MW | Asymmetrical flashing relay – 0.02 s..300 h – 24..240 V AC – 2 OC
Schneider RE48ACV12MW – Asymmetrical Flashing Relay
1. Overview
The Schneider RE48ACV12MW is a multi-function asymmetrical flashing relay from the RE48 series. It is designed to alternate between ON and OFF states for user-defined durations, making it suitable for time-delay applications in industrial automation. Its wide timing range and multi-voltage capability make it highly flexible for various control system requirements.
2. Technical Specifications
-
Product Series: RE48
-
Function: Asymmetrical flashing relay (ON and OFF times can be set independently)
-
Timing Range:
-
Adjustable from 0.02 seconds to 300 hours
-
Both ON and OFF times are independently adjustable
-
-
Supply Voltage Range:
-
24 to 240 V AC (wide voltage input range)
-
-
Output Contacts:
-
2 changeover contacts (2 CO / SPDT)
-
Rated at 8 A (resistive load)
-
-
Output Type: Electromechanical relay
-
Power Consumption: ≤ 3.5 VA
-
Repeat Accuracy: ± 0.5%
-
Mounting: DIN rail or panel mounting
-
Connection Type: Screw clamp terminals
-
Front Panel Interface:
-
Potentiometers for time setting (ON and OFF)
-
LED indicators for output status
-
-
Standards and Certifications:
-
CE, UL, CSA, RoHS compliant
-
-
Protection:
-
IP20 (housing), IP50 (front face)
-
Overvoltage and short-circuit protection
-
3. Applications
The RE48ACV12MW is suitable for a variety of industrial and commercial applications requiring precise ON/OFF control with flexible timing intervals:
-
Industrial Automation: For cyclic control of machinery or systems where different ON and OFF cycles are required.
-
Lighting Control: Flashing lights, warning beacons, or signage systems with defined flashing intervals.
-
Pump Control Systems: Alternating pump operation cycles (e.g., irrigation or water treatment).
-
Alarm Systems: Creating pulse signals or intermittent alerts for alarms or warning signals.
-
Motor Control: Starting and stopping motors in timed sequences for load balancing or alternating usage.
-
Process Control: Automating periodic tasks in manufacturing or assembly processes.
4. Key Features
-
Wide Timing Range: Easily configurable from milliseconds to several hours for versatile applications.
-
Dual Time Settings: Asymmetrical timing lets you independently set different durations for ON and OFF states.
-
Multi-Voltage Input: Accepts a broad voltage range, simplifying inventory and compatibility across systems.
-
Compact Design: Fits standard 48 x 48 mm panel cutouts and DIN rail systems.
-
Reliable Performance: High-precision timing with excellent repeat accuracy.
-
Visual Indicators: LED status indicators provide real-time operational feedback.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | Harmony Timer Relays |
|---|---|
| Electrical connection | Plug-in sub-base 11 pin(s) |
| Width | 48 mm |
| Product or component type | Panel-mounted/plug-in timer relay |
| Discrete output type | Relay |
| Contacts type and composition | 2 C/O timed contacts, AgNi (cadmium free) |
| Component name | RE48A |
| Time delay range | 0.2...12 min 5...300 s 0.02...1.2 s 0.5...30 min 5...300 h 0.2...12 h 0.2...12 s 0.5...30 s 2...120 s 0.05...3 s 2...120 min 5...300 min 0.5...30 h 2...120 h |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz |
| Voltage range | 0.85...1.1 Us AC 0.9...1.1 Us DC |
| [In] rated current | 5 A |
| Product front plate size | 48 x 48 mm |
|---|---|
| Control type | Selector switch front panel |
| Housing material | Self-extinguishing |
| Repeat accuracy | +/- 0.2 % of the maximum setting value conforming to IEC 61812-1 |
| Temperature drift | +/- 0.02 %/°C of the maximum setting value conforming to IEC 61812-1 |
| Voltage drift | +/- 0.2 %/V of the maximum setting value at 48...240 V +/- 1 %/V of the maximum setting value at 24...48 V |
| Setting accuracy of time delay | +/- 5 % of full scale at 25 °C conforming to IEC 61812-1 +/- 10 % of full scale at 25 °C conforming to IEC 61812-1 |
| Time delay type | Asymmetrical flashing - L- Asymmetrical flashing relay (starting pulse-off) Asymmetrical flashing - Li- Asymmetrical flashing relay (starting pulse-on) |
| Minimum pulse duration | 20 ms |
| Reset time | 25 ms on de-energisation |
| Pick up duration | 55 ms |
| On-load factor | 100 % |
| Power consumption in VA | 6 VA at 240 V |
| Power consumption in W | 2 W at 240 V |
| Breaking capacity | 1250 VA |
| minimum switching current | 100 mA |
| Maximum switching current | 5 A |
| Maximum switching voltage | 250 V AC/DC |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Output voltage | 240 V at 5 A AC-12 30 V at 2 A DC-13 240 V at 1.5 A AC-15 |
| Marking | CE |
| Surge withstand | 1 kV differential mode conforming to IEC 61000-4-5 level 3 2 kV common mode conforming to IEC 61000-4-5 level 3 |
| Mounting support | Base mounted: socket Panel mounted: system supplied with the product |
| Local signalling | 1 LED (yellow) for output relay state LED indicator (green) for flashing: relay energised timing in progress LED indicator (green) for on steady: relay energised, no timing in progress |
| Function available | L- Asymmetrical flashing relay (starting pulse-off)-2 C/O Li- Asymmetrical flashing relay (starting pulse-on)-2 C/O |
| Control type | Without test button |
| Net weight | 0.14 kg |
| Shape of pin | Cylindrical |
| Number of functions | 2 |
| Humidity drift | +/- 0.05 %/%RH of the maximum setting value conforming to IEC 61812-1 |
|---|---|
| Immunity to microbreaks | 5 ms |
| Dielectric strength | 2 kV 1 mA/1 minute conforming to IEC 61812-1 |
| Protection against electric shocks | 4 kV class III conforming to IEC 60664-1 4 kV class III conforming to IEC 61812-1 |
| Standards | EN 50081-1/2 EN 50082-1/2 IEC 61812-1 93/68/EEC 89/336/EEC IEC 60669-2-3 73/23/EEC |
| Product certifications | UL C-Tick cULus CSA |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| IP degree of protection | IP40 (housing) conforming to IEC 60529 IP50 (front face) conforming to IEC 60529 |
| Vibration resistance | 0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6 |
| Relative humidity | 93 % without condensation conforming to IEC 60068-2-3 |
| Resistance to electrostatic discharge | 6 kV in contact conforming to IEC 61000-4-2 level 3 8 kV in air conforming to IEC 61000-4-2 level 3 |
| Resistance to electromagnetic fields | 10 V/m 26 MHz to 1 GHz conforming to IEC 61000-4-3 level 3 |
| Resistance to fast transients | 2 kV (direct) conforming to IEC 61000-4-4 level 3 4 kV (direct) conforming to IEC 61000-4-4 level 4 |
| Immunity to radioelectric fields | 10 V (0.15...80 MHz) conforming to IEC 61000-4-6 level 3 |
| Immunity to voltage dips | 30 % / 10 ms conforming to IEC 61000-4-11 95 % / 5 s conforming to IEC 61000-4-11 60 % / 100 ms conforming to IEC 61000-4-11 |
| Disturbance radiated/conducted | Class B 0.15...30 MHz conforming to EN 55022 (EN 55011 group 1) |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.700 cm |
| Package 1 Width | 10.300 cm |
| Package 1 Length | 6.200 cm |
| Package 1 Weight | 131.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.417 kg |
| Warranty | 18 months |
|---|