Schneider RE7TM11BU | on-delay timing relay with control contact – 0.05..1 s – 24 V AC DC – 1OC
Schneider RE7TM11BU | on-delay timing relay with control contact – 0.05..1 s – 24 V AC DC – 1OC
Description
Schneider RE7TM11BU | on-delay timing relay with control contact – 0.05..1 s – 24 V AC DC – 1OC
1. Technical Specifications
-
Model: Schneider RE7TM11BU
-
Type: On-delay timing relay with control contact
-
Timing Range: 0.05 to 1 second
-
Control Voltage: 24 V AC/DC
-
Relay Contact Configuration: 1 normally open contact (1OC)
-
Mounting Type: Rail-mountable
-
Housing Material: Thermoplastic
-
Protection Rating: IP20 (protection against solid objects >12 mm, no protection against water)
2. Features
-
Precise Timing Function: The relay offers an adjustable time delay range from 0.05 to 1 second, allowing for fine-tuned timing control in various automation tasks.
-
Versatile Control Voltage: Designed to operate with 24 V AC/DC control voltage, providing compatibility with a wide range of low-voltage control systems.
-
Reliable Contact Configuration: Equipped with a 1 normally open contact (1OC), suitable for initiating or controlling other circuits when the timing function is completed.
-
Space-Saving Design: Compact design for rail mounting, making it easy to integrate into control panels, electrical cabinets, and other automation systems.
-
Durable Construction: Made with thermoplastic materials, ensuring the relay is robust and suitable for use in industrial environments.
-
User-Friendly Adjustments: The timing range can be easily set within the specified range, allowing flexibility for various applications.
3. Applications
-
Automation Systems: Ideal for use in time delay circuits where a precise time interval needs to be introduced before activating a subsequent action or process.
-
Control Panels: Commonly used in control panels to manage various processes that require a specific time delay before activation, such as in motor start/stop sequences or lighting control.
-
Industrial Equipment: Can be used in industrial machines to delay the activation of certain equipment or processes, ensuring proper sequence timing.
-
HVAC Systems: Useful in HVAC applications for delaying certain actions like the operation of pumps or fans to maintain system stability.
-
Signal and Alarm Systems: Can be applied to alarm and signaling systems where an action needs to be delayed before being triggered.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | Zelio Time |
|---|---|
| Product or component type | Industrial timing relay |
| Component name | RE7 |
| time delay type | Aw A At |
| time delay range | 0.05 s...300 h |
| Discrete output type | Relay |
|---|---|
| Contacts material | 90/10 silver nickel contacts |
| Width pitch dimension | 22.5 mm |
| [Us] rated supply voltage | 110...240 V AC 50/60 Hz 24 V AC/DC 50/60 Hz 42...48 V AC/DC 50/60 Hz |
| Voltage range | 0.85...1.1 Us |
| Connections - terminals | Screw terminals, 2 x 1.5 mm² flexible with cable end Screw terminals, 2 x 2.5 mm² flexible without cable end |
| Tightening torque | 0.6…1.1 N.m |
| Setting accuracy of time delay | +/- 10 % of full scale |
| Repeat accuracy | +/- 0.2 % |
| Temperature drift | < 0.07 %/°C |
| Voltage drift | < 0.2 %/V |
| Minimum pulse duration | 20 ms |
| Reset time | 50 ms |
| Maximum switching voltage | 250 V AC/DC |
| Mechanical durability | 20000000 cycles |
| [Ith] conventional free air thermal current | 8 A |
| Maximum [Ie] rated operational current | 2 A DC-13 24 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 0.1 A DC-13 250 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 0.2 A DC-13 115 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 3 A AC-15 at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 |
| Minimum switching capacity | at 12 V 10 mA |
| Input voltage | < 60 V X1Z2 terminal(s) < 60 V Y1Z2 terminal(s) |
| Maximum switching current | 1 mA (X1Z2) 1 mA (Y1Z2) |
| Input compatibility | 3/4 wires sensors PNP/NPN without internal load <50 m X1Z2 terminal(s) 3/4 wires sensors PNP/NPN without internal load <50 m Y1Z2 terminal(s) |
| Potentiometer characteristic | Linear 47 kOhm (+/- 20 %), 0.2 W, cable length <25 m Z1Z2 terminal(s) |
| Marking | CE |
| Overvoltage category | III conforming to IEC 60664-1 |
| [Ui] rated insulation voltage | 250 V between contact circuit and control inputs IEC certified 250 V between contact circuit and power supply IEC certified 300 V between contact circuit and control inputs CSA certified 300 V between contact circuit and power supply CSA certified |
| Supply disconnection value | > 0.1 Uc |
| Operating position | Any position without derating |
| Surge withstand | 2 kV conforming to IEC 61000-4-5 level 3 |
| Power consumption in VA | 0.7 VA at 24 V 1.6 VA at 48 V 1.8 VA at 110 V 8.5 VA at 240 V |
| Maximum power consumption in W | 0.5 W at 24 V 1.2 W at 48 V |
| Terminal description | ALT (X1)UNUSED (B1-A2)CO (15-16-18)OC_OFF (Z2)UNUSED (Y1)UNUSED (Z1)UNUSED |
| Height | 78 mm |
| Width | 22.5 mm |
| Depth | 80 mm |
| Net weight | 0.15 kg |
| Immunity to microbreaks | 3 ms |
|---|---|
| Standards | EN/IEC 61812-1 |
| Product certifications | CSA GL UL |
| Ambient air temperature for storage | -40…85 °C |
| Ambient air temperature for operation | -20…60 °C |
| Relative humidity | 15…85 % 3K3 conforming to IEC 60721-3-3 |
| Vibration resistance | 0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| IP degree of protection | IP20 (terminals) IP50 (housing) |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Dielectric strength | 2.5 kV |
| Non-dissipating shock wave | 4.8 kV |
| Resistance to electrostatic discharge | 6 kV in contact conforming to IEC 61000-4-2 level 3 8 kV in air conforming to IEC 61000-4-2 level 3 |
| Resistance to electromagnetic fields | 10 V/m conforming to IEC 61000-4-3 level 3 |
| Resistance to fast transients | 2 kV conforming to IEC 61000-4-4 level 3 |
| Disturbance radiated/conducted | CISPR 11 group 1 - class A CISPR 22 - class A |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider NSYSFD2010 | Spacial SF plain door – 2000×1000 mm
Schneider NSYSFC66 | Spacial SF bottom and top frame – 600×600 mm
Schneider NSYSFV20 | Set of 4 vertical uprights for Spacial SF enclosure. Height: 2000 mm. RAL 7035.
Schneider NSYSM1810402D | PanelSeT SM compact enclosure without mounting plate – 1800x1000x400 mm
-
0
Schneider LE1D25Q7 | Enclosed DOL starter,TeSys LE,25A,380V AC coil,including 1 LC1D,2 pushbuttons
-
0
Reviews